Reason and Treatment of Water Shortage in Biomass Steam Generator

2020-09-16 10:24:42
second

Biomass steam generator Cause of water shortage: water supply equipment or pipeline failure. Unable to timely feed water into the boiler, causing biomass Steam generator Lack of water. The stoker did not monitor the water level enough. When the load of biomass steam generator increases, the adjustment is not timely or is used incorrectly. The water level alarm and interlock protection device have failed to detect in time. The stoker misjudged the water level. Do not know the false water level formed when the load of biomass steam generator changes suddenly, do not distinguish the false water level caused by improper installation of water level gauge, blockage of steam water channel, inadequate steam water cock switch and other reasons, and do not distinguish the water level of biomass boiler clearly due to water shortage or full water.

How to deal with water shortage of biomass steam generator: check the water level indicated by each water level gauge to correctly judge whether the biomass steam generator is short of water. When it is impossible to determine whether the biomass steam generator is full or short of water, the drain cock of the water level gauge can be opened. If no boiler water flows out, it indicates a water shortage accident, otherwise it is a full water accident.    

The water hole of the water connecting pipe of the water level gauge is higher than the high fire boundary of the heating surface and the biomass steam generator with large water capacity. Otherwise, the biomass steam generator cannot be called for water, because it will delay the treatment time of the water shortage accident of the biomass steam generator.

When the biomass steam generator is slightly short of water, reduce fuel and air supply, weaken combustion, and slowly feed water to the biomass steam generator to normal water level. Generally, the inlet flow rate and water supply volume are controlled by adjusting the opening and size of the water supply valve, and attention shall be paid not to excessive water inflow. Then check whether the biomass steam generator is abnormal, and run the biomass steam generator after confirming that it is normal.   

When the biomass steam generator is seriously short of water, emergency fire extinguishing and boiler shutdown are required. And do not water into the pot. When the biomass steam generator is cooled by natural ventilation and the water temperature in the boiler drops below 70 ℃, the water can enter slowly. Check the biomass steam generator after the water inlet reaches the normal level, and restart the ignition and run the biomass steam generator if there is no abnormality.    

Biomass steam generator If the biomass steam generator is not handled carefully after water shortage, it will be damaged, and serious injuries will be caused. Therefore, the biomass steam generator should be handled carefully according to the steps after water shortage.

 Biomass steam generator